OUTPUT VOLTAGE RIPPLE SUPPRESSION OF HIGH VOLTAGE POWER SUPPLY FOR IONISING RADIATION DETECTION UNITS
Abstract and keywords
Abstract (English):
Operation and results of tests of operating model of high-voltage power supply of ionizing radiation detection units with active suppression of output voltage pulsations are described. The joint effect of the smoothing RC-filter and the circuit of active pulsation suppression on the value of their amplitude was experimentally investigated. The device was tested at an output voltage of 1 kV and a load current of 1 mA. The minimum peak-to-peak ripple amplitude achieved does not exceed 1mV.

Keywords:
voltage source, high voltage, multiplication circuit, voltage ripple, filtering, operational amplifier, feedback, compensating signal, active suppression
Text
Publication text (PDF): Read Download
References

1. Artyuh A.G., Kononenko G.A., Salamatin A.V., Sereda Yu.M. Precizionnye istochniki vysokogo napryazheniya dlya detektorov yadernogo izlucheniya na transformatorah POL-12012 (KST-POL-12012). Preprint «Ob'edinennogo instituta yadernyh issledovaniy». Dubna, 2022. URL: http://www1. jinr.ru/Preprints/2022/033(P13-2022-33).pdf (data obrascheniya: 17.04.2024).

2. Kolobov V.V., Barannik M.B. Precizionnyy maloshumyaschiy istochnik vysokogo napryazheniya//Pribory i tehnika eksperimenta. 2021. № 6. S. 15-24.

3. Operacionnyy usilitel' ADA4817. URL: https://www.alldatasheet.com/datasheet-pdf/ pdf/254592/AD/ADA4817-1.html (data obrascheniya: 20.03.2024).

4. Bufer BUF634T. URL: https://static.chipdip.ru/lib/248/DOC000248423.pdf (data obrascheniya: 19.03.2024).